MASSA PRODUCTS CORPORATION June 11, 2013
Product Manual 20 M3 Wireless Ultrasonic Level Sensor
13) Reboot the gateway to have the settings
take affect by selecting Administration
Reboot, then click on the Reboot button.
This will take approximately 1 minute.
14) Verify if the Python code is active by
entering the Management Connections
menu. If the python code
Python:massa_gateway_appl.py does not
appear under the title Protocol, then you
may have to reboot again or check to see if
is it enabled in the Auto-start Settings
menu as seen on Step 12.
15) Turn on the M3 Sensor and wait for it to
associate itself to the gateway (brief flash
every 2 seconds). If it does not associate,
press the sensor’s Commission button
once. Click on the Configuration XBee
Network menu and press the Refresh
button to see the sensor on the device list.
Once you have established the sensor on
the ZigBee network, you can proceed to
installing the M3 Application Software,
see next page. Note that the Node ID will
indicate sensor model type (from the
XBee’s NI register).